K0363 K363: Install corridor and hallway doors that block smoke.
E

Deficiencies in Corridor Door Maintenance

Gardens At Stevens, TheStevens, Pennsylvania Survey Completed on 03-31-2025

Summary

The facility was found to have deficiencies related to the maintenance of corridor doors, which are crucial for fire safety and smoke containment. On March 31, 2025, an observation revealed that the stairtower doors on the 1st floor, near Resident Room 215, had gaps greater than the allowed 3/16 inch. This was confirmed by an interview with the Director of Maintenance, indicating that the doors exceeded the permissible gap margins, thus failing to meet the National Fire Protection Association (NFPA) 101 standards for corridor doors. Additionally, further observations on the same day revealed that the corridor doors to Resident Rooms 215 and 205 failed to close and latch properly. These findings were also confirmed through interviews with the Director of Maintenance. The inability of these doors to close and latch compromises their effectiveness in resisting the passage of smoke, which is a critical safety requirement, especially in fully sprinklered smoke compartments. These deficiencies highlight a failure in maintaining the required safety standards for corridor doors within the facility.

Plan Of Correction

1. The corridor doors to Resident Rooms 205 and 215 have been adjusted to close and latch. 2. The corrective action was completed on 4/1/2025. 3. The Maintenance Director or Designee will conduct a facility wide audit of all facility corridor doors for closure and latch then random door checks monthly. 4. Findings of Audits will be submitted to QAPI for review.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0363 citations
Failure of Corridor Door to Latch Properly
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that a corridor door to a resident room on one floor failed to latch into the frame when tested, meaning it did not meet NFPA 101 requirements for positive latching of corridor doors. The Facilities Manager and Facility Life Safety staff confirmed during interview that this corridor door did not latch properly.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Multiple Corridor Door Deficiencies Impacting Smoke and Fire Protection
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors identified several corridor door deficiencies, including doors that failed to latch, lacked smoke tight integrity, and had missing locksets, across multiple floors. These issues were confirmed by facility leadership during the exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Properly Latching Corridor Doors
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two corridor doors, one on the third floor and one on the second floor, did not latch when tested, affecting two smoke compartments. The Facility Administrator and Maintenance Director confirmed these deficiencies, which were not in compliance with fire and smoke protection requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Positive Latching of Corridor Door
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

A corridor door leading to the Patio Lounge failed to positively latch within the door frame, as observed and confirmed by the Director of Maintenance. This deficiency affected one of twelve smoke compartments and did not meet NFPA 101 and CMS requirements for corridor door latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Corridor Doors for Smoke Resistance and Latching
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that corridor doors to two resident rooms did not close and latch properly, as confirmed by the facility's Administrator and Maintenance Director. This deficiency affected one of five smoke compartments and did not meet regulatory requirements for smoke resistance and positive latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Corridor Doors Failed to Latch in Smoke Compartment
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Two corridor doors, serving resident rooms in a smoke compartment, were found to be stuck in their frames and unable to fully latch, as confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙