K0900 K900: Meet Health Care Facilities Code mechanical requirements.
F

Deficient Nurse Call System Maintenance

Westlake Nursing And Rehab CenterDania Beach, Florida Survey Completed on 03-14-2025

Summary

The facility failed to maintain its nurse call system in accordance with NFPA 99 standards, as observed during a fire safety tour conducted on March 14, 2025. At the West Nurse's Station, which serves rooms 1-20, the required nurse call visual signal was missing at the corridor intersection near the nurse's station, where individual resident room doors are not directly visible. Additionally, the annunciator panel for Room 14 did not light up, and there was no audible signal when tested. Similarly, at the East Nurse's Station, which serves rooms 21-35, the required nurse call visual signal was also missing at the corridor intersection. The annunciator panels for Rooms 29, 31, and 32 did not light up, and there was no audible signal for Rooms 31 and 32 when tested. These deficiencies were acknowledged by the Administrator and the Maintenance Director during the observations and were reviewed with them at the exit conference.

Plan Of Correction

Facility denies and disputes the validity of this citation and completes this POC solely to meet the requirements of State licensure and Federal regulations. Facility further denies any and all statements, acknowledgements, confirmations, or comments attributed to facility staff as strictly hearsay. 1) What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice; Identified nurse call system visual signal on West and East Nurses station; quotes obtained by an outside vendor 2/19/2025. Parts ordered 3/31/2025 for the nurse call system in accordance with NFPA 99 to be completed by 4/14/2025 based upon vendor availability for installation. (2) How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Quality review completed by the ED/Maintenance designee r/t ensuring the nurse call light system is maintained according to NFPA 99 to be completed by 4/14/2025. (3) What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; Maintenance re-educated by the ED r/t ensuring the nurse call light system is maintained according to NFPA 99 to be completed by 4/14/2025. (4) How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place; Ongoing quality monitoring to be completed by the ED/Maintenance/designee through visual observation to ensure the nurse call light system is maintained according to NFPA 99 weekly x 4 weeks, twice monthly x 2 weeks then monthly and PRN as indicated.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0900 citations
Deficient Nurse Call System Maintenance
F
K0900 K900: Meet Health Care Facilities Code mechanical requirements.
Short Summary

The facility's nurse call systems in the Galilee and Masada wings were found deficient during a fire safety tour, with several corridor lights failing to illuminate as required by NFPA 99 standards. The Maintenance Director acknowledged these deficiencies.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙