K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
E

Hazardous Area Enclosure Deficiency

Harmar Village Health & Rehab CenterCheswick, Pennsylvania Survey Completed on 03-17-2025

Summary

The facility failed to maintain hazardous area enclosures, as evidenced by an observation on March 17, 2025. During the inspection, it was noted that the door to the transfer switch room, located across from the boiler room, did not latch properly when tested. This deficiency affected one of the eight smoke compartments in the facility. The issue was confirmed through an interview with the Facility Administrator and Maintenance Director on the same day.

Plan Of Correction

The Nursing Home Administrator (NHA) provided re-education to the Maintenance Director on 0321 Hazardous Area Enclosures. The door to the transfer switch room was repaired and now latches as appropriate. The Maintenance Director completed an audit of hazardous area enclosures and no other noncompliant areas were identified. The Maintenance Director will complete a random audit of hazardous area enclosures weekly times two weeks then monthly times 2 months.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0321 citations
Failure to Maintain Self-Closing Doors for Multiple Hazardous Storage Areas
F
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that multiple hazardous storage areas, including a closet near medical records, a beauty salon used to store chemical cases, a supply room in one nursing station, a room leading to a smoking area, a housekeeping room near therapy, and a lobby storage room, lacked required self-closing or automatic-closing doors. These conditions did not comply with NFPA 101 requirements for hazardous area enclosure and had the potential to affect all residents and staff in an emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Soiled Linen Room Door Failed to Latch in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that the common area soiled linen room on the second floor, classified as a hazardous area in a sprinklered location, had a door that failed to positively latch when tested. This door is required to self-close and latch to maintain proper separation for hazardous areas. The issue was confirmed with the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Fire Barrier Door Closure in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

A faulty door closure was observed on the South Nurses' Station and Food Storage Room, resulting in the door failing to automatically close and latch as required for hazardous area enclosures. This deficiency was confirmed by the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Self-Closing and Latching Door in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that the door to a third-floor trash room, classified as a hazardous area, did not self-close or positively latch as required. This issue was confirmed by facility staff during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hazardous Area Door Deficiencies and Improper Hold-Open Devices
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors identified that hazardous area doors, including the Sprinkler Tank Room and 1st floor Dietary Storage Room, were not maintained within required gap margins and were held open with unauthorized devices, as confirmed by the Director of Facilities.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hazardous Area Door Failed to Self-Close and Latch
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

A deficiency was found when the A Hall Resident Care Supply room door did not self-close to a positive latch as required by LSC 8.7.1.3, leaving a hazardous area inadequately protected according to fire safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙