K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
E

Fire/Smoke Barrier Deficiency

Menorah HouseBoca Raton, Florida Survey Completed on 03-19-2025

Summary

The facility failed to maintain their fire/smoke barrier construction in accordance with NFPA 101 standards. During a fire safety tour conducted on March 19, 2025, with the Maintenance Director, surveyors observed penetrations in the fire/smoke barriers at two locations within the facility. Specifically, at 12:52 PM, a penetration was found through both sides of a 2-hour fire-rated wall in the Galilee wing near Room 233. Additionally, at 2:09 PM, another penetration was identified through both sides of a smoke wall in the Masada wing near Room 127. The Maintenance Director acknowledged these findings during the tour, and the observations were reviewed with both the Administrator and the Maintenance Director at an exit conference later that day. The report notes that these examples are not exhaustive, suggesting that other unprotected penetrations may exist within the facility's fire/smoke barriers. It emphasizes the importance of conducting a thorough inspection of each barrier along its full length and height to ensure all penetrations are identified and properly sealed. The report underscores the necessity of maintaining the integrity of fire and smoke barriers to restrict the movement of fire and smoke, thereby ensuring the safety of the facility's occupants in the event of a fire emergency. It specifies that any breaches in fire-rated barriers must be repaired using a UL-listed approved system to restore the original fire or smoke-rated integrity of the walls, ceilings, or floors involved.

Plan Of Correction

NFPA 101 SUBDIVISION OF BUILDING SPACES SMOKE BARRIER 1. What corrective action(s) will be accomplished for those residents found to have been affected by the practice: 1) In the allegation of the Galilee wing, near room 233 having one penetration through both sides of the smoke wall. Maintenance will seal the penetration with Red Fire Caulk. 2) In the allegation of the Masada wing, near room 127 having one penetration through both sides of the smoke wall. Maintenance will seal the penetration with Red Fire Caulk. 2. How you will identify other residents having potential to be affected by the same practice and what corrective action will be taken: All residents in the facility have the potential to be affected by these practices. 3. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur: Maintenance will seal the alleged penetration in the smoke walls with Red Fire caulk. 4. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put into place: The Director of Maintenance or a qualified Designee, will monitor for substantial compliance. Findings of the audits will be reported at the Monthly QAPI meeting by the Director of Maintenance or a qualified Designee to ensure effectiveness and compliance of the plan of correction. Corrective action completion date: 4/19/25 K372 SUBDIVISION OF BUILDING SPACES-SMOKE BARRIER 1. What corrective action(s) will be accomplished for those residents found to have been affected by the practice: 1) In the allegation of the Galilee wing, near room 233 having one penetration through both sides of the smoke wall. Maintenance will seal the penetration with Red Fire Caulk. 2) In the allegation of the Masada wing, near room 127 having one penetration through both sides of the smoke wall. Maintenance will seal the penetration with Red Fire Caulk. 2. How you will identify other residents having potential to be affected by the same practice and what corrective action will be taken: All residents in the facility have the potential to be affected by these practices. 3. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur: Maintenance will seal the alleged penetration in the smoke walls with Red Fire caulk. 4. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put into place: The Director of Maintenance or a qualified Designee, will monitor for substantial compliance. Findings of the audits will be reported at the Monthly QAPI meeting by the Director of Maintenance or a qualified Designee to ensure effectiveness and compliance of the plan of correction.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0372 citations
Improper Repair of Smoke Barrier Penetrations in Multiple Smoke Compartments
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire-rated enclosures were not properly maintained, with penetrations in smoke barriers in several general storage rooms across multiple smoke compartments. The Maintenance Director stated that insulation and fiberglass were used to pack and cover these holes but could not confirm that the materials were approved for fire-rated construction. Inspectors observed penetrations covered with fiberglass and noted a hole in one fiberglass panel in a storage room, resulting in a deficiency under NFPA 101 requirements for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetrations in Smoke/Fire Barriers After Electrical Work
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire barriers in three of fourteen smoke compartments, including the hot water room, the barrier between the kitchen and a smoke compartment, and the smoke wall leading to the Alzheimer’s unit, had penetrations that were not properly fire-stopped. During the on-site interview, the Maintenance Director acknowledged that recent electrical work had been completed and that the contractor failed to seal these penetrations, resulting in noncompliance with NFPA 101 smoke barrier construction requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

A deficiency was identified when an unsealed penetration around data wires was observed in a smoke barrier wall on the second floor near the Rehabilitation Department. This issue was confirmed by the Administrator and Maintenance Director and affected one of two floors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unprotected Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

An unprotected penetration was found in a smoke barrier wall above double doors near the ADON/Medical Records Office, where blue and red wires passed through without proper protection. This issue, confirmed by the Director of Maintenance, affected two of twelve smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Wire Penetrations in Smoke Barrier
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that two wires passed unsealed through a smoke barrier above the ceiling near a resident corridor, with the Maintenance Director confirming unawareness of the sealing requirement. This deficiency had the potential to affect five residents and did not comply with NFPA 101-2012 standards for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Smoke Barrier Integrity per NFPA 101
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found multiple penetrations in smoke barriers sealed with non-fire-rated materials and one unsealed pipe, compromising the required fire and smoke resistance in several corridors and the attic. Maintenance leadership confirmed uncertainty about the materials used, and these deficiencies had the potential to affect all 39 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙