K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
D

Fire Extinguisher Obstructions and Installation Issues

Menorah HouseBoca Raton, Florida Survey Completed on 03-19-2025

Summary

The facility failed to comply with NFPA 101 standards for portable fire extinguishers, as evidenced by observations made during a fire safety tour. Specifically, three out of twelve sampled portable fire extinguishers were not installed or maintained correctly. At 12:00 PM, a class ABC fire extinguisher in the Telecommunication Equipment Room was obstructed by equipment, and at 12:02 PM, the same room lacked a clean agent fire extinguisher. Additionally, at 12:55 PM and 1:22 PM, fire extinguishers near Rooms 203 and 209 were obstructed by carts, respectively. These deficiencies were confirmed through an interview with the Maintenance Director, who acknowledged the findings during the tour. The issues were further discussed with the Administrator and the Maintenance Director at an exit conference. Photographic evidence was obtained to support these observations, and the facility's non-compliance with NFPA 10 and NFPA 101 standards was documented.

Plan Of Correction

K355 NFPA 101 PORTABLE FIRE EXTINGUISHERS 1. What corrective action(s) will be accomplished for those residents found to have been affected by the practice: 1) In the allegation of ABC fire extinguisher in the Telecommunication Equipment Room being obstructed by equipment. Maintenance has moved items around to ensure that the ABC fire extinguisher is unobstructed. 2) In the allegation of the Telecommunications room not having a clean agent fire extinguisher. Maintenance will place a clean agent fire extinguisher in the Telecommunication room. 3) In the allegation of the fire extinguisher near room 203 being obstructed by a cart. The cart was moved. An in-service will be done for the staff not to place carts in front of fire extinguishers. 4) In the allegation of the fire extinguisher near room 209 being obstructed by a cart. The cart was moved. An in-service will be done for the staff not to place carts in front of fire extinguishers. 2. How you will identify other residents having potential to be affected by the same practice and what corrective action will be taken: All residents in the facility have the potential to be affected by these practices. 3. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur: Maintenance will ensure that in the Telecommunication room that the ABC fire extinguisher is not obstructed. Maintenance will put a clean agent fire extinguisher in the Telecommunication room. Maintenance will in-service staff not to place carts in front of fire extinguishers. Maintenance will ensure that carts are not placed in front of fire extinguishers during rounds. 4. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put into place: The Director of Maintenance or a qualified Designee will monitor for substantial compliance. Findings of the audits will be reported at the Monthly QAPI meeting by the Director of Maintenance or a qualified Designee to ensure effectiveness and compliance of the plan of correction. Corrective action completion date: 4/19/25 K355 PORTABLE FIRE EXTINGUISHERS 1. What corrective action(s) will be accomplished for those residents found to have been affected by the practice: 1) In the allegation of ABC fire extinguisher in the Telecommunication Equipment Room being obstructed by equipment. Maintenance has moved items around to ensure that the ABC fire extinguisher is unobstructed. 2) In the allegation of the Telecommunications room not having a clean agent fire extinguisher. Maintenance will place a clean agent fire extinguisher in the Telecommunication room. 3) In the allegation of the fire extinguisher near room 203 being obstructed by a cart. The cart was moved. An in-service will be done for the staff not to place carts in front of fire extinguishers. 4) In the allegation of the fire extinguisher near room 209 being obstructed by a cart. The cart was moved. An in-service will be done for the staff not to place carts in front of fire extinguishers. 2. How you will identify other residents having potential to be affected by the same practice and what corrective action will be taken: All residents in the facility have the potential to be affected by these practices. 3. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur: Maintenance will ensure that in the Telecommunication room that the ABC fire extinguisher is not obstructed. Maintenance will put a clean agent fire extinguisher in the Telecommunication room. Maintenance will in-service staff not to place carts in front of fire extinguishers. Maintenance will ensure that carts are not placed in front of fire extinguishers during rounds. 4. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put into place: The Director of Maintenance or a qualified Designee will monitor for substantial compliance. Findings of the audits will be reported at the Monthly QAPI meeting by the Director of Maintenance or a qualified Designee to ensure effectiveness and compliance of the plan of correction.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0355 citations
Blocked Portable Fire Extinguisher Identified
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher next to a resident room was found to be blocked during an observation, and this was confirmed by facility leadership during the exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Monthly Fire Extinguisher Inspections
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation confirming that basement portable fire extinguishers were inspected monthly as required, with no records available for several months. This was confirmed by the Administrator during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation for annual fire extinguisher maintenance and technician certification, and a fire extinguisher in the main kitchen was found blocked. These deficiencies were confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers per NFPA 10
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not ensure portable fire extinguishers were properly inspected and maintained according to NFPA 10, with one extinguisher lacking inspection records and another found overpressurized. These issues were confirmed by the Maintenance Director and could impact 15 occupants.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Accessibility of Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

Surveyors found that 12 out of 18 portable fire extinguishers were installed with the top of the handle positioned above the sixty-inch maximum height allowed by NFPA 101 and NFPA 10, with some as high as sixty-three inches. In one case, a trash can obstructed access to a fire extinguisher cabinet. The Maintenance Director acknowledged these findings during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Fire Extinguisher Maintenance Documentation
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher in the kitchen service hallway was found without the required monthly maintenance and inspection tag, indicating a failure to document compliance with NFPA 10 standards. This was confirmed by the Maintenance Director and Administrator during surveyor interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙