Deficiency in Common Wall Door Maintenance

Fox Subacute At MechanicsburgMechanicsburg, Pennsylvania Survey Completed on 01-23-2025

Summary

The facility failed to maintain the integrity of common wall doors on the second floor, as observed during a survey on January 23, 2025. Specifically, the common wall door at the bridge to the elevator had gaps greater than 1/8 inch, which exceeds the allowed gap margins. This deficiency was confirmed through an interview with the Director of Maintenance, who acknowledged that the door did not meet the required standards. Additionally, another observation on the same day revealed that common wall doors on the second floor by the East Lounge also had gaps greater than 1/8 inch and lacked manual positive latching. These doors were only held closed by a coded magnetic release, which allowed them to open freely when the fire alarm was activated. The Director of Maintenance confirmed these findings, indicating that the doors did not comply with the necessary safety requirements.

Plan Of Correction

1. The distance between the common wall doors by the East lounge have been adjusted and corrected to meet one-eighth-inch requirement. 2. Door was adjusted to ensure manual positive latching. 3. Facility Maintenance Director or his designee will audit random doors for gaps for the next 3 months and then quarterly. 4. Maintenance Director will report findings to the QAPI committee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0133 citations
Noncompliant Fire-Rated Separation Door Between Multiple Occupancies
E
K0133
Short Summary

Surveyors identified that a fire-rated separation door between building levels did not meet NFPA 101 multiple occupancy requirements. Initially, the basement separation door had holes where panic hardware had been removed and only a turning knob remained, compromising the door’s fire-rated function. On revisit, although panic hardware had been installed, the door still failed to latch properly in the frame due to friction. Facility leadership and maintenance staff acknowledged these door deficiencies.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire-Rated Door Deficiency in Smoke Compartment
D
K0133
Short Summary

The facility failed to maintain a fire-rated door separating Nursing Care from Assisted Living, compromising fire safety. The door had been modified, resulting in gaps and unauthorized repairs, affecting one of ten smoke compartments. The Director of Plant Operations confirmed these deficiencies.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Door Deficiency Due to Lack of Bottom Latching
E
K0133
Short Summary

The facility failed to maintain the fire resistance rating of fire doors on the first floor due to the absence of a bottom latching device. This issue was initially observed and confirmed during an inspection in December and remained unresolved during a follow-up revisit in February.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Barrier Deficiencies on First Floor
E
K0133
Short Summary

The facility failed to maintain fire resistance on one of three floors. Observations revealed unsealed penetrations around data lines and malfunctioning double doors by the Staff Development Office, which did not close or latch properly and had broken hardware. These issues were confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance of Common Walls
D
K0133
Short Summary

The facility did not maintain the fire resistance of common walls, affecting one smoke compartment. Observations revealed four unprotected penetrations in the wall separating the 01 and 02 Components, located above the ceiling and doors. Three penetrations were around wires, and one was empty. The Maintenance Manager confirmed these findings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Door Deficiency Due to Lack of Bottom Latching
E
K0133
Short Summary

The facility failed to maintain the fire resistance rating of fire doors, as observed when a fire door on the first floor lacked bottom latching. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙