K0311 K311: Have an enclosure around a vertical opening shaft.
D

Vertical Opening Enclosure Deficiency

St Barnabas Nursing HomeGibsonia, Pennsylvania Survey Completed on 01-23-2025

Summary

The facility failed to maintain the required fire resistance rating for vertical opening enclosures, specifically affecting one of the 15 smoke compartments. During an observation, it was noted that multiple data, cable, and electrical wires were passing through a large open hole in the back corner of Room U 115. This deficiency was confirmed through an interview with the Facility Administrator and Maintenance Director, who acknowledged the issue with the vertical opening enclosure.

Plan Of Correction

Assuming for the sake of this discussion, the validity of the deficiencies noted in the Department of Health's Statement of Deficiencies Report to St. Barnabas Nursing Home, Inc for the survey ending January 23, 2025, which St. Barnabas does not admit, we offer the following Plan of Correction. Nothing contained in the Plan of Correction shall/should be deemed an admission either expressed or implied, on the part of St. Barnabas Nursing Home, Inc. as to the validity of the deficiencies noted in the report. 1. Facility maintenance will purchase and install the proper electrical tray and fire blocking material around cables, data lines, and electrical wires in U115 on or before March 14, 2025. 2. Director of maintenance or designee will perform a one-time audit of the building ensuring all data, cable, and electrical wires passing through vertical openings are properly sealed. 3. Results of the audit will be reviewed in QA.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0311 citations
Failure to Maintain Self-Closing Mechanism on Laundry Chute Door
B
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

A basement laundry chute door was found to lack the required number of fusible links on its hold-open springs, preventing the door from closing as mandated. This deficiency was confirmed by both the administrator and maintenance supervisor during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance Rating for Vertical Openings
B
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain the required fire resistance rating for vertical openings, affecting two levels. The stairway between the Lower Level Kitchen and the First Floor lacked one-hour fire resistive construction. Additionally, the north side exit from the Basement had a staircase with unsheathed walls, lacking the required fire resistance. These deficiencies were confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Vertical Opening Enclosures
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain proper vertical opening enclosures, as unsealed openings were found in a bathroom pipe chase wall on two unoccupied floors. This was due to ongoing work to replace a leaking drain pipe, affecting two smoke compartments. The issue was confirmed by the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance Rating on Tenth Floor
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility did not maintain the fire resistance rating of vertical openings on the tenth floor. An observation revealed that the rated access ceiling door in the Electrical Closet next to room 1020 failed to self-close and latch, as confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Fire Resistance in Vertical Enclosures
C
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain the required fire resistance rating for vertical enclosures, affecting all six floors. Observations revealed that HVAC shafts adjacent to exit stair towers lacked the necessary two-hour fire resistance. Additionally, the Clay Street exit stair tower on the fourth and fifth floors had inadequate construction, with insufficient drywall and unprotected steel beams. This deficiency was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Vertical Opening Fire Safety Deficiency
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain fire safety for a vertical opening between two floors. The self-closing devices were removed from the Private Dining Room's double doors, which are part of a one-hour, two-story vertical opening. This deficiency was confirmed during an interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙