K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
F

Failure to Maintain and Inspect Portable Fire Extinguishers

St Monica Center For Rehabilitation & HealthcarePhiladelphia, Pennsylvania Survey Completed on 01-23-2025

Summary

The facility failed to maintain and inspect portable fire extinguishers as required by NFPA 101 and NFPA 10 standards. During a document review, it was found that the facility could not provide certification for the technician responsible for the annual maintenance and inspection of the fire extinguishers. Additionally, observations revealed that several fire extinguishers were obstructed by storage items in various locations, including the first floor dining room, across from the 500 wing Nurses' Station, and in the basement housekeeping storage area. Furthermore, the indicator lights for recessed mounted fire extinguishers were not functioning in multiple areas throughout the facility. The facility also neglected to conduct monthly inspections of portable fire extinguishers in several locations, with some not inspected since October or November 2024, and one in the Elevator Machine Room not inspected since July 2024. Additionally, a fire extinguisher in the Basement Elevator Machine Room was found not mounted to the wall. These deficiencies were confirmed during an exit interview with the Administrator and Maintenance Director.

Plan Of Correction

1. The certificate of the technician conducting the annual inspection has been obtained from the vendor. Blocked fire extinguisher in the main dining room, across from the 500-unit nurses' station and housekeeping storage in the basement has been exposed and the area cleared. Indicator lights for recessed portable fire extinguishers are maintained lit. Fire extinguisher monthly checks have been scheduled for maintenance. The basement elevator machine room fire extinguisher is mounted on the wall. 2. NHA/Designee to in-service maintenance staff on the requirement of maintenance and inspection of fire extinguishers monthly, ensuring they remain free from obstruction, and the indicator display is properly functioning. 3. The Maintenance director/Designee has completed an inspection of fire extinguishers in the building to ensure they are stored, functioning, and the display indicator is properly visible. 4. The maintenance director/designee will conduct a random audit (10 total) of the fire extinguishers monthly x 3 to ensure they are properly maintained, inspected, and the indicator display is properly functioning. 5. Results of audits will be reported to QA.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0355 citations
Blocked Portable Fire Extinguisher Identified
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher next to a resident room was found to be blocked during an observation, and this was confirmed by facility leadership during the exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Monthly Fire Extinguisher Inspections
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation confirming that basement portable fire extinguishers were inspected monthly as required, with no records available for several months. This was confirmed by the Administrator during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation for annual fire extinguisher maintenance and technician certification, and a fire extinguisher in the main kitchen was found blocked. These deficiencies were confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers per NFPA 10
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not ensure portable fire extinguishers were properly inspected and maintained according to NFPA 10, with one extinguisher lacking inspection records and another found overpressurized. These issues were confirmed by the Maintenance Director and could impact 15 occupants.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Accessibility of Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

Surveyors found that 12 out of 18 portable fire extinguishers were installed with the top of the handle positioned above the sixty-inch maximum height allowed by NFPA 101 and NFPA 10, with some as high as sixty-three inches. In one case, a trash can obstructed access to a fire extinguisher cabinet. The Maintenance Director acknowledged these findings during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Fire Extinguisher Maintenance Documentation
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher in the kitchen service hallway was found without the required monthly maintenance and inspection tag, indicating a failure to document compliance with NFPA 10 standards. This was confirmed by the Maintenance Director and Administrator during surveyor interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙