K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
E

Electrical System Deficiencies in Facility

Wyndmoor Hills Rehabilitation And Nursing CenterWyndmoor, Pennsylvania Survey Completed on 01-27-2025

Summary

The facility failed to maintain electrical equipment, as observed during a survey on January 27, 2025. The deficiencies were noted on two of the four levels of the facility. In the basement boiler room, an unsecured junction box was found resting on top of the middle boiler. On the second floor, above the smoke doors near the nurses' station, electrical tape was improperly used to secure a junction box cover instead of using appropriate screws. Additionally, in the Activities Department, an electric baseboard heater was improperly placed on top of an abandoned heating register, with exposed Romex wiring, and surrounded by combustible materials, including cardboard. These observations were confirmed during an exit interview with the Administrator and Maintenance Director on the same day.

Plan Of Correction

1. The open junction box in the basement boiler room was immediately secured. Appropriate screws were installed on the second floor, above the smoke doors to the left of the nurses' station, to secure a junction box. The heater inside the Activities Department was repaired to ensure compliance. 2. Electrical equipment throughout the facility audited to ensure compliance. 3. Education will be provided to ensure proper compliance with this regulation. 4. An audit of the junction box in the boiler room and the heater in the Activities Department will be conducted to ensure compliance. Audit will be done 2x a month for 2 months and 1x a month for 1 month. 5. The findings of these quality monitoring's to be reported to the Quality Assurance/Performance Improvement Committee monthly x6 months.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0911 citations
Open Breaker Slot Found in Generator Room Electrical Panel
D
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Surveyors observed that the generator room contained an electrical breaker panel labeled "Panel HC" with an open breaker slot, indicating the electrical system was not maintained per NFPA 70 and NFPA 99 requirements. During an interview, the maintenance supervisor confirmed this electrical system deficiency in one of the facility’s smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Panel Blocked by Cart in Nurse Station Supply Closet
E
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

An electrical panel inside the nurse station supply closet was found to be blocked by a large cart, making it inaccessible in violation of NFPA 70 requirements. This was confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Wiring Protection Deficiencies Identified
E
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Surveyors identified multiple deficiencies in the protection of electrical wiring, including broken receptacle cover plates, open junction boxes, open wires not ending in a junction box, and unsecured electrical outlets in two smoke compartments. These issues were confirmed by facility leadership and cited as non-compliant with NFPA 70 and NFPA 99 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical System Maintenance Deficiencies Identified
E
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Surveyors found that a receptacle near an A-bed was missing a cover and a reading light over another A-bed had exposed, non-terminated wiring hanging from the underside of the cover. These electrical system deficiencies were confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Outlet Multipliers for Heat Tape
D
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Heat tape installed on the building was found plugged into outlet multipliers outside the main entrance, which was confirmed as a deficiency by the maintenance supervisor during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical System Deficiencies: Exposed Wiring and Inaccessible Panels
E
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Surveyors identified deficiencies in electrical system maintenance, including an open junction box with exposed wiring and electrical panels blocked by storage or with a broken latch, which remained unresolved upon revisit.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙