K0923 K923: Have proper medical gas storage and administration areas.
B

Improper Storage of Oxygen Cylinders in Staff Lounge

Cranberry PlaceCranberry Township, Pennsylvania Survey Completed on 01-29-2025

Summary

The facility failed to maintain proper storage of medical gas cylinders in one of its rooms, specifically the staff lounge. During an observation on January 29, 2025, it was noted that oxygen cylinders were stored without being separated or labeled as full or empty. This lack of organization and labeling is a direct violation of the requirements for medical gas cylinder storage, which mandates that empty cylinders be segregated from full ones to avoid confusion. An interview with the maintenance supervisor on the same day confirmed the deficiencies in the storage of oxygen cylinders. The supervisor acknowledged the improper storage practices, which did not comply with the standards set forth for medical gas cylinder management. This oversight in maintaining the storage protocol could potentially lead to safety hazards, although the report does not specify any immediate consequences or risks.

Plan Of Correction

Oxygen tanks storage of full tanks immediately labeled full tanks. Nursing staff educated on the need to keep signage in place. Audits will be weekly. Results will be reviewed at the QAPI meeting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0923 citations
Failure to Maintain Required Oxygen Cylinder Storage and Secured Storage Room
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen storage requirements were not maintained when a freestanding oxygen cylinder was observed unsecured in a third-floor room and the C-Hall oxygen storage room door failed to close and latch due to a coordinator malfunction. The Maintenance Director confirmed these oxygen storage deficiencies during the survey exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage of Oxygen Cylinders Near Combustibles
F
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors observed that more than 12 "E" oxygen cylinders (18 total) were stored in a sprinkler room within five feet of combustible materials, contrary to NFPA 99 requirements for gas equipment cylinder storage. The Maintenance Director confirmed this storage practice during the survey. This noncompliance with NFPA 99 sections 11.3.1–11.3.3 was cited as a deficiency affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Room Cautionary Signage
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that an oxygen storage room on the second floor lacked the required precautionary signage stating, "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING," as mandated for gas cylinder storage areas. This deficiency was confirmed by facility leadership during the initial survey and again during a subsequent revisit, when the same room was still missing the required sign.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Oxygen Cylinder Storage Near Combustibles and Electrical Receptacles
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders stored within first- and second-floor nurses' stations were placed less than five feet from electrical receptacles and combustible materials, in violation of NFPA 99/101 requirements for separation of oxidizing gases from combustibles and ignition sources. The Administrator and Maintenance Director confirmed during interview that the cylinders were improperly stored in proximity to these combustible and ignition sources.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Signage in Crash Cart Rooms
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders were stored in crash cart rooms in two separate cores without the required precautionary signage on the doors indicating oxidizing gas storage and no smoking. Observations in two smoke compartments showed oxygen cylinders present in the 3 East and 2 East core crash cart rooms, yet the doors lacked the mandated "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING" signage. The facility administrator and maintenance leadership confirmed that the proper oxygen storage signs were not posted on these doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage and Security of Gas Cylinders
D
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that gas cylinders were improperly stored and unsecured, with 38 cylinders in an outside storage room lacking the required oxidizing gas signage and with full and empty cylinders comingled, and an additional 25 cylinders stored adjacent to this area without any means to prevent unauthorized access. During an interview, the Maintenance Director acknowledged the issues and reported being unaware of the specific NFPA 99 storage requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙