K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
E

Unsealed Penetrations in Smoke Barriers

University City Rehabilitation And Healthcare CtrPhiladelphia, Pennsylvania Survey Completed on 01-22-2025

Summary

The facility failed to maintain the fire resistance of smoke barriers, which is a requirement for ensuring safety in the event of a fire. During an observation on January 22, 2025, unsealed penetrations by data wires were found in the smoke barriers at two locations within the facility. The first unsealed penetration was observed on the second floor near resident room 257 at 10:02 a.m., and the second was on the first floor near resident room 172 at 10:19 a.m. This deficiency was confirmed during an exit interview with the Administrator and the Maintenance Director on the same day at 10:30 a.m.

Plan Of Correction

Maintenance director was in serviced on checking that all penetrations are properly sealed. Areas identified have been resolved by maintenance director by sealing penetrations around data wires with 3M Fire Barrier Sealant (CP 25WB+). All areas will be reviewed by maintenance director to assure that there are no open penetrations around data wires. Maintenance Director/Designee will monitor all areas to ensure that there are no open penetrations around data wires 3 times per week for 4 weeks and 1 time per month for 2 months. Results will be brought to QAPI and variances will be addressed.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0372 citations
Improper Repair of Smoke Barrier Penetrations in Multiple Smoke Compartments
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire-rated enclosures were not properly maintained, with penetrations in smoke barriers in several general storage rooms across multiple smoke compartments. The Maintenance Director stated that insulation and fiberglass were used to pack and cover these holes but could not confirm that the materials were approved for fire-rated construction. Inspectors observed penetrations covered with fiberglass and noted a hole in one fiberglass panel in a storage room, resulting in a deficiency under NFPA 101 requirements for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetrations in Smoke/Fire Barriers After Electrical Work
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire barriers in three of fourteen smoke compartments, including the hot water room, the barrier between the kitchen and a smoke compartment, and the smoke wall leading to the Alzheimer’s unit, had penetrations that were not properly fire-stopped. During the on-site interview, the Maintenance Director acknowledged that recent electrical work had been completed and that the contractor failed to seal these penetrations, resulting in noncompliance with NFPA 101 smoke barrier construction requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

A deficiency was identified when an unsealed penetration around data wires was observed in a smoke barrier wall on the second floor near the Rehabilitation Department. This issue was confirmed by the Administrator and Maintenance Director and affected one of two floors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unprotected Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

An unprotected penetration was found in a smoke barrier wall above double doors near the ADON/Medical Records Office, where blue and red wires passed through without proper protection. This issue, confirmed by the Director of Maintenance, affected two of twelve smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Wire Penetrations in Smoke Barrier
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that two wires passed unsealed through a smoke barrier above the ceiling near a resident corridor, with the Maintenance Director confirming unawareness of the sealing requirement. This deficiency had the potential to affect five residents and did not comply with NFPA 101-2012 standards for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Smoke Barrier Integrity per NFPA 101
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found multiple penetrations in smoke barriers sealed with non-fire-rated materials and one unsealed pipe, compromising the required fire and smoke resistance in several corridors and the attic. Maintenance leadership confirmed uncertainty about the materials used, and these deficiencies had the potential to affect all 39 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙