Deficient Fire Separation in Facility Occupancies

Hartwyck At Oak TreeEdison, New Jersey Survey Completed on 12-20-2024

Summary

The facility failed to ensure that sections of health care facilities classified as other occupancies were properly separated from areas of healthcare occupancies by construction with a two-hour fire resistance rating. This deficiency was identified during observations and interviews conducted on December 19, 2024. Specifically, the separation between the Healthcare occupancy and the Residential occupancy was compromised by a 1.5-inch and 2.5-inch unprotected penetration for wire pass-throughs. Additionally, a 2-inch-high by 48-inch-wide section of brick was missing above the fire-rated door assembly between the two occupancies. These observations were confirmed by the USTFOTAT at the time of the inspection. The facility's representative was informed of these deficient practices during the Life Safety Code exit conference on December 20, 2024.

Plan Of Correction

1/9/25 1. All residents have the potential to be affected by this deficient Life Safety Code. The maintenance department repaired the 2 unprotected penetrations for the pass-through of wires on 1/8/25 using UL listed NUEX Order 26.4(DX LC 150 fire-stop sealant. The maintenance department repaired the 2 inch by 48 inch wide section of brick missing above the fire rated door assembly between the two occupancies on 1/8/25 using intumescent fire-stop pillows and UL listed NJ Ex Order 26.4(15) LC 150 fire-stop sealant. 2. The facility's maintenance schedule will be revised by the Director of Maintenance to include a monthly inspection of fire-rated assemblies between the healthcare occupancy and the residential occupancy to confirm that the two hour fire resistance rating is intact with no penetrations using an audit tool. 3. The Director of Maintenance will review the fire rated assembly inspection reports monthly ongoing and report the results to the administrator and to the QAPI committee monthly for 6 months.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0131 citations
Failure to Maintain Fire-Resistant Door Barriers
E
K0131
Short Summary

Surveyors identified that fire-rated doors in the basement elevator lobby area had multiple penetrations and extensive damage, compromising the required fire resistance rating for common wall separations. Facility leadership confirmed these deficiencies during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Building Separation
E
K0131
Short Summary

The facility failed to maintain proper building separation in sections classified as other occupancies. An observation revealed that the doorway to Country House, between skilled nursing and assisted living, lacked a 1 1/2 hour fire-resistant door. This deficiency was confirmed during an exit interview with the Administrator and the Director of Maintenance, acknowledging the lack of complete two-hour fire-resistant separation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance Rating in Facility
D
K0131
Short Summary

The facility failed to maintain a two-hour fire resistance rating between the main building and the west wing due to a door that did not latch properly, affecting one of the smoke compartments. This deficiency was confirmed by the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance Rating in Common Walls
E
K0131
Short Summary

The facility did not maintain the fire resistance rating of common walls, as observed by an unsealed penetration around data wires above the doors separating Willowbrooke Court and the Independent Living Unit. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance in Common Wall Separations
E
K0131
Short Summary

The facility failed to maintain fire resistance in common wall separations as certain fire-rated doors did not positively bottom latch. Observations revealed that the double doors at Tony's Café and a level fire door in the basement, both separating different components, failed to latch properly. This was confirmed during an exit interview with the Facility Administrator and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Resistance Deficiency in Facility
E
K0131
Short Summary

The facility failed to maintain the fire resistance rating of common wall fire separations, affecting one of three levels. The rated double doors near the basement loading dock did not fully close and positively latch when tested. This was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙